  1. (c.) 5/1 ratio - To find turns-ratio divide the higher voltage by the lower voltage 120v/24v = 5.

  2. (c.) 20.83 amps - To find secondary current use ohms law formula I = W/E = 500w/24v = 20.83a.

  3. (b.) 4.16 amps - To find the primary current I = W/E = 500va/120v = 4.16 current in the primary.

  4. (a.) 500 va - To find the input va at 100% efficiency it is equal to the output va which is 500.